APCUSPd CentOS 6.5
This guide will let you configure apcupsd using PCNET broadcasts from the UPS network management card.
Prerequisites:
- EPEL repo
- APC UPS with network management card 2, firmware 6.1.1.
Configure APC network management card to allow PCNET connection
PCNET is UDP broadcast communication over port 3052. If you use a firewall, open communication for this port.
- Configuration → Shutdown, disable Basic Signaling Shutdown.
- Configuration → Shutdown, enter 16 character shutdown phrase.
- Configuration → Shutdown, username: device.
- Configuration → PowerChute clients → add client IP address.
Install and configure apcupsd
- Install apcupsd.
yum install apcupsd
- Autostart apcupsd after boot.
chkconfig apcupsd on
- Configure apcupsd. Edit /etc/apcupsd/apcupsd.conf.
UPSNAME SMART750 UPSCABLE ether UPSTYPE pcnet DEVICE 1.2.3.4:apc:1234567890123456 # Your 16 char shutdown phrase. BATTERYLEVEL 10 # Issue shutdown at or below 10% battery. MINUTES 10 # If runtime left is 10 minutes or below, shutdown.
- Open UDP 3052 from UPS to server. Edit /etc/sysconfig/iptables
-A INPUT -m state --state NEW -m udp -p udp --dport 3052 -j ACCEPT
- Restart iptables.
service iptables restart
- SELinux: Allow bind to port 3052. This should be fixed in newer versions of CentOS.
yum -y install policycoreutils-python setenforce 0 # clear the audit log cd /var/log/audit echo > audit.log service apcupsd start service apcupsd stop setenforce 1 cp audit.log /var/tmp cd /var/tmp audit2allow -M myapcupsd < audit.log semodule -i myapcupsd.pp
- Start apcupsd.
service apcupsd start
Test
- Wait 30 seconds for the PCNET broadcast and test access.
apcaccess