Check_MK - local check APCUSPd
This simple script, using the apcaccess command, checks for:
- APC-check (if apcaccess runs OK)
- APC-status (on battery or not)
- APC-load
- APC-batt-temp
#!/bin/bash apcaccess="/sbin/apcaccess" tempout="/dev/shm/apcaccess.out" # remove old output rm "$tempout" # generate new status $apcaccess > $tempout ecode="$?" if [[ $ecode -eq "0" ]]; then echo "0 APC-check - apcaccess run OK" else echo "3 APC-check - apcaccess run, exit code: $ecode" fi # read through output, generate statistics seperator=":" cat $tempout | while read line do before=`echo ${line%%"$seperator"*} | xargs` # xargs will strip whitespace after=`echo ${line#*"$seperator"} | xargs` case $before in STATUS) if [[ "$after" -eq "ONLINE" ]]; then echo "0 APC-status - APC UPS Online" else echo "2 APC-status - APC UPS not online, status: $after" fi ;; LOADPCT) pct=`echo $after | cut -d " " -f1` if [[ `bc <<< "$pct<70"` -eq "1" ]]; then echo "0 APC-load loadpct=$pct APC UPS Load: $pct%" else echo "2 APC-load loadpct=$pct APC UPS Load: $pct%" fi ;; ITEMP) deg=`echo $after | cut -d " " -f1` if [[ `bc <<< "$deg<24"` -eq "1" ]]; then echo "0 APC-batt-temp btemp=$deg APC UPS battery temperature: $deg deg. C." else echo "1 APC-batt-temp btemp=$deg APC UPS battery temperature: $deg deg. C." fi ;; esac done